IVL-RE low voltage filter reactor
Picture display
Summary
Technical parameter

Product Introduction

In the low-voltage reactive power compensation system, the capacitor is the core component in the reactive power compensation cabinet. In addition to the impact of the use environment, the life of the capacitor is also very important due to its harmonic current, closing inrush current and long-term overvoltage. Directly cause damage to the capacitor, so a certain proportion of reactors in series in front of the capacitor to suppress and absorb some harmonics and ensure the safety and stability of the compensation loop is the most common method at present.

After the IVL-RE series low-voltage filter reactors are connected in series with capacitors, they can suppress harmonic amplification and filter out a certain proportion of harmonics. After precise matching, they are connected in series with capacitors to form a passive filter, which can accurately filter out certain harmonics. At the same time, it suppresses the inrush current when the capacitor is put in, and protects the capacitor and other components.

 

Features

●Dry-type iron core design, using high-quality silicon steel sheet, strong overcurrent capability
●Strong harmonic suppression capability
●Low loss, low noise
●Long service life
●Pure dry structure, resin casting
●With 120℃ secondary protection temperature control switch
●Humidity resistance, excellent flame retardant performance
●Small size, light weight, more convenient installation
●Strong corrosion resistance, stable electrical performance
项   目 具 体 参 数
Rated voltage of supporting capacitor 280V,300V,480V,525V,815 V,880V
Reactance rate  7.0%,  14% and non-standard customization
Winding material High-quality low-loss pure copper (T2) or high-quality aluminum
Phase Single phase, three phase
Rated frequency 50Hz, 60Hz
Stable overcurrent 1.8 In
Withstand voltage test Winding to ground 3kV/1 minute
Inductance 0≤LN≤5%
Temperature rise Coil temperature rise 70K
loss ≤15w/kvar
Operating temperature -40 ℃ ~ 50 ℃
Operating environment Humidity 90%
thermal control 65 ℃ normally open, 120 ℃ normally closed
Insulation temperature class Class H
noise ≤ 48dB
Protection level IP00 ,Indoor installation
Linearity 1.8 In
Installation distance > 50mm