Home
About
Product
News
Contact
Service
Language
IVM-900 Power Quality Online Monitoring Device
Picture display
Summary
Technical parameter

Product Introduction

IVM-900 series power quality online monitoring device is a device for real-time monitoring of power quality of the power grid. It has harmonic analysis, waveform sampling and voltage swell/swell recording, flicker monitoring, voltage unbalance measurement, and waveform transient Capture, event recording, measurement control functions, etc. Using high-brightness LCD Chinese man-machine interface display, a new generation of ARM processor and high-speed ADC sampling, 1024 points per week can be sampled, and the basic measurement accuracy can reach 0.1 level. The IVM-900 power quality online monitoring device has high measurement accuracy, rich measurement functions, strong anti-interference, and simple and convenient operation.

Product Features

Function type Features
Monitoring function Three-phase voltage, zero sequence voltage Three-phase current, zero sequence current
Three-phase active power and total active power
Three-phase reactive power and total reactive power
Three-phase apparent and total apparent power
Positive and negative active power measurement
Four-quadrant reactive power measurement
Harmonic electricity measurement
Three-phase power factor and total power factor
frequency
Data event
Record function
Event record data record
Monitoring power limit
Function type Features
Power Quality
Monitoring function
Three-phase voltage deviation and over-limit alarm
Frequency deviation and over-limit warning
Voltage fluctuation analysis
Short-term flicker Pst calculation
Long-term flicker Plt calculation
Harmonic distortion rate calculation and limit violation alarm
Three-phase voltage/current unbalance measurement
The amplitude and phase of the voltage zero sequence, negative sequence, and positive sequence components
The amplitude and phase of the current zero sequence, negative sequence, and positive sequence components
The effective value, phase angle, content rate and harmonic power voltage, current and power spectrum diagram of 2~63th harmonic
High-speed fault recorder

 

Main parameters and technical indicators

Types of parameter
Power supply 100VAC/DC~240VAC/DC
Power consumption <20W
Analog quantity acquisition 1024 points per week
monitor 7-inch color LCD display, touch screen operation
Communication Communication interface: 2 RS485
Communication protocol: Modbus-RTU
Communication rate: 2400/4800/9600/19200/38400
57600/115200bps
Communication interface: 1 RS232
Communication rate: 2400/4800/9600/19200/38400
/57600/115200bps
Communication interface: Ethernet
Communication protocol: Modbus-TCP
Default port number: 502
Switch input Passive node optically isolated input (isolation voltage 2500VDC)
Types of parameter
Relay output Electromagnetic relay, contact capacity 5A/30VDC or 5A/250VAC; hold time: 0~600s, 0 means constant hold
Analog input Voltage measurement: AC voltage 100V and 380V input
Choose one of the two ranges 0~1.2Ue, Ue is the voltage rating
Current measurement: 5A, range: 0~6.000A
Current measurement: 1A, range: 0~1.200A
Rated frequency: 50Hz, range: 45Hz~65Hz
SOE record System event, limit violation event, transient event, I/O event, waveform event
working environment Temperature: -5℃~+55℃; Humidity: 95% non-condensing;
Air pressure: 70~106kpa
storage temperature -30℃~+80℃
Protection level Panel: IP50; Shell: IP20
Types of parameter
Mean time between failures MTBF≥43800 hours
Dimensions 248×171×204 (width × height × depth) unit mm