IVL-CAP low voltage power capacitor
Picture display
Summary
Technical parameter

Product Introduction


IVL-CAP series low-voltage power capacitors are cylindrical capacitors using metalized polypropylene film technology (MKP technology), with good self-healing properties; it uses a new generation of dry technology to achieve environmental protection, safety, and miniaturization of capacitors , The installation is more convenient, the installation space is saved, and the flammable and explosive hidden dangers caused by oil leakage of traditional capacitors are completely solved.

IVL-CAP series low-voltage power capacitors are mainly used for reactive power compensation to improve the power factor. When used with series reactance, they can also suppress harmonics, reducing line losses and reducing line losses for power supply systems and users. The important role of improving equipment utilization is one of the important core components to improve power quality.

 

Features

●Cylindrical aluminum housing
●Dry capacitors
●Safety and explosion-proof performance
●Low loss of capacitors
●Excellent self-healing performance
●Long service life
●Good heat dissipation, small size and light weight
●Customized terminal assembly method is more convenient
●Adopt international advanced winding machine to ensure the stability and consistency of each product
Item Parameter
Rated voltage 280-880V, 50/60HZ
Overvoltage 1.1 Un(long),1.15Un(30min), 1.3 Un(5min)
Overcurrent 1.3InLong run
Interelectrode withstand voltage 2.15Un , 5SNo breakdown
Polar shell withstand voltage 3600Vac , No breakdown in 2 seconds
Dielectric High quality polypropylene film
Capacitance tolerance -5% ~+10%
Dielectric loss ≤0.1W/kvar
Safety features Dry technology, overpressure separator, self-healing, over-temperature protection
Discharge time With discharge resistance, discharge to below 75 volts within 3 minutes after power off
external structure Cylindrical aluminum metal shell with safety bolts at the bottom
Environmental temperature difference -40/D; Maximum temperature +55℃, daily average highest +45℃, annual average highest +35℃, lowest -40℃
cooling method Natural cooling or forced cooling
Install the device Any position, the bottom bolt is grounded
Relative humidity ≤95%
altitude Conventional 2000 meters, higher altitude can be customized
Protection level IP20, indoor assembly (assembled with the cover, meets IP54)
Service life >200 , 000h
technical standard GB/T12747.1-2017;GB/T12747.2-2017
IEC 60831-1:2014;IEC60831-2:2014